WK - HEAT EXCHANGERS (water duct heating systems)

Heat exchangers for duct heating systems form a seperate group of products in water heating
In objects with windows reaching the floor and objects of special requirements (e.g. objects of historical value, churches, etc.), heating systems composed of convectors installed in ducts made in floor are used.
As the system may be installed at any place, it is not obtrusive to the interior design and also positively affects it's aesthetics.
Ducts also provide uniform heat distribution to the entire room.


WK-P
Basic dimensions
WK-L
Basic dimensions

Specification "WK-P" and "WK-L"

Type
WK-P
WK-L
Dimensions

Water capacity

Radiator weight
Normal thermal power (*)
acc.to EN-442 75/65/20oC
lenght L
ribbed part lenght B
height H
cm
dm3
kg
W
  5
49
36
WK-P1
0,183
 
WK-L
0,102
0,36
3,4
289
  6.5
64
50
0,46
4,4
395
  8
79
65
0,56
5,4
509
  9.5
94
81
0,66
6,3
628
  11
109
96
0,76
7,3
739
  12.5
124
111
0,86
8,2
850
  14
139
126
0,96
9,2
960
  15.5
154
141
1,06
10,1
1069
  17
169
155
1,16
11,1
1170
  18.5
184
170
1,26
12,0
1279
  20
199
185
1,36
13,0
1387
  21.5
214
201
1,46
13,9
1502
  23
229
216
1,56
14,8
1609
  24.5
244
231
1,66
15,7
1716
  26
259
246
1,76
16,6
1823
  27.5
274
261
1,86
17,5
1929
  29
289
275
1,96
18,3
2028

Specification "WK-P2" (double exchangers)

Type
WK-P2
Dimensions

Water capacity

Radiator weight
Normal thermal power (*)
acc.to EN-442 75/65/20oC
lenght L
ribbed part lenght B
height H
cm
dm3
kg
W
  5
57
36
0,183
0,72
6,3
589
  6.5
72
50
0,92
8,3
806
  8
87
65
1,12
10,3
1038
  9.5
102
81
1,32
12,1
1281
  11
117
96
1,52
14,1
1508
  12.5
132
111
1,72
15,9
1734
  14
147
126
1,92
17,9
1958
  15.5
162
141
2,12
19,7
2181
  17
177
155
2,32
21,7
2387
  18.5
192
170
2,52
23,5
2609
  20
207
185
2,72
25,5
2829
  21.5
222
201
2,92
27,3
3064
  23
237
216
3,12
29,1
3282
  24.5
252
231
3,32
30,9
3500
  26
267
246
3,52
32,7
3719
  27.5
282
261
3,72
34,5
3935
  29
297
275
3,92
36,1
4137

The maximum working temperature: 95oC
The maximum working pressure 1,0 MPa (up to 3,0 MPa on special orders)
 (*) For selection of radiators for parameters other than 75/65/20°C,
      use the GPM and GCM radiator   correction indexes.