Convector "PRESTIGE GPM" and "PRESTIGE GCM" - water radiators

These radiators, with their discreet, box-like casing, show off as elegant designs and will satisfy needs of both users and interior designers. They are suitable for every type of premises, residential and business alike, wherever thermal comfort and aesthetics of the rooms are equally observed.

The "Prestige" radiators feature very durable structure.

External surfaces of radiators are made of aluminium and are covered with polyester-epoxy enamels in the powder technology. This ensures durability of the radiator working even in rooms of increased humidity, e.g. in swimming pool halls, bath facilities, laundries, etc.

Additionally, the "Prestige Plus" version is offered by the Convector company, a radiator with a case reinforced with and additional board, for the rooms where the radiator may be exposed to mechanical damages (e.g. staircases).


offers the following water radiator types:

  "PRESTIGE GPM" - are radiators with side water supply
  "PRESTIGE GCM" - are radiators with bottom water supply


Bottom-fed radiators (GCM) are fitted with the Danfoss
RTD-N thermostatic valve with the maximum water flow as the default setting.
Danfoss RTD thermostatic heads may be connected to this valve.

PRESTIGE GPM and GCM radiators higher than 20 cm and longer than 70 cm are suited for installing an air humidifier.
All water radiators are fitted with an air vent.
 
Specification and basic dimensions

Type
GPM
GCM
Dimensions Water capacity Radiator weight Normal thermal power(**)
acc.to EN-442
75/65/20°C
Length L Height H GPM GCM GPM GCM
cm dm3 kg W
    2/4 40 20 0,12 0,13 3,3 3,8 191
    2/5,5 55 20 0,17 0,18 4,2 4,7 281
    2/7 70 20 0,21 0,22 5,2 5,6 377
    2/8,5 85 20 0,26 0,27 6,1 6,5 476
    2/10 100 20 0,30 0,31 7,0 7,5 580
    2/11,5 115 20 0,35 0,36 7,9 8,4 687
    2/13 130 20 0,39 0,40 8,9 9,3 797
    2/14,5 145 20 0,44 0,45 9,8 10,2 910
    2/16 160 20 0,48 0,49 10,7 11,1 1025
    2/17,5 175 20 0,53 0,54 11,6 12,1 1143
    2/19 190 20 0,57 0,58 12,6 13,0 1263
 
    4/4 40 40 0,25 0,29 4,9 5,4 362
    4/5,5 55 40 0,34 0,38 6,3 6,8 533
    4/7 70 40 0,43 0,47 7,7 8,2 714
    4/8,5 85 40 0,52 0,56 9,1 9,6 903
    4/10 100 40 0,61 0,65 10,5 11 1100
    4/11,5 115 40 0,70 0,74 11,9 12,5 1303
    4/13 130 40 0,79 0,83 13,3 13,9 1512
    4/14,5 145 40 0,88 0,92 14,8 15,3 1725
    4/16 160 40 0,97 1,01 16,2 16,7 1944
    4/17,5 175 40 1,06 1,10 17,6 18,1 2167
    4/19 190 40 1,15 1,19 19,0 19,5 2394
 
    6/4 40 60 0,37 0,44 6,5 7,1 527
    6/5,5 55 60 0,51 0,58 8,4 9,0 775
    6/7 70 60 0,64 0,71 10,3 10,9 1038
    6/8,5 85 60 0,78 0,85 12,2 12,8 1313
    6/10 100 60 0,91 0,98 14,1 14,6 1599
    6/11,5 115 60 1,05 1,12 15,9 16,5 1894
    6/13 130 60 1,18 1,25 17,8 18,4 2198
    6/14,5 145 60 1,31 1,39 19,7 20,3 2508
    6/16 160 60 1,45 1,52 21,6 22,2 2826
    6/17,5 175 60 1,53 1,65 23,5 24,1 3150
    6/19 190 60 1,72 1,79 25,4 26,0 3480
 
    8/4 40 80 0,50 0,60 8,1 8,7 687
    8/5,5 55 80 0,68 0,78 10,5 11,1 1011
    8/7 70 80 0,86 0,96 12,9 13,5 1354
    8/8,5 85 80 1,04 1,14 15,2 15,8 1713
    8/10 100 80 1,21 1,32 17,6 18,2 2085
    8/11,5 115 80 1,39 1,49 20,0 20,6 2470
    8/13 130 80 1,57 1,67 22,4 23,0 2860
    8/14,5 145 80 1,75 1,85 24,8 25,4 3271
    8/16 160 80 1,93 2,03 27,1 27,8 3686
    8/17,5 175 80 2,11 2,21 29,5 30,1 4108
    8/19 190 80 2,29 2,39 31,9 32,5 4539

Report from the ITGiS Radom research No. 120 and 121/2001/LA
The maximum working pressure 1.0 MPa (GPM up to 3.0 MPa on special orders)
The maximum working temperature 95°C
GPM and GCM radiators are produced only to specific orders: delivery time - 21 days

 (*) For selection of radiators for parameters other than 75/65/20°C,
      use the GPM and GCM radiator   correction indexes.

Basic dimensions:

The outlet grate, with its properly shaped elements, performs the function of a drive for the heated air leaving the radiator. The structure of the outlet grate allows placing it so that the outlet air is directed to the centre of the room.

The coil pipe of water radiators is made of copper, while elements of ribs making up the case are made of aluminium.
Only the coil pipe is in contact with the installation water in Convector radiators.

Selection of water radiators should be made based on the calculation of heat demand. This requires calculations of design nature and should be performed by a designer or an experienced installer.
The proprietary OZC, Instal-c.o. Convector software is recommended.